Application of VS 300
11
Doku-Version 2.05 - Firmware 2.10 - 15. September 2017
3
Application of VS 300
The VS 300 Pack Controller is designed for controlling small to medium refrigeration compressor packs and
condensers. It contains its own user interface with 4-digit 7-segment LED display and is suitable for stand-alone
use. When expanded by an optional CAN bus module, it can be fully integrated into the LDSWin remote moni
toring system. Additionally, it can be combined with an optional alarm module containing two alarm relays (Prior
ity 1 and Priority 2).
For the compressor pack and condenser the VS 300 provides the following functions:
S
Control and regulation
S
Fault reporting
S
Fault archiving
S
Monitoring
S
Archiving
These functions are as follows:
Pressure control with two freely configurable control loops for one or two independent refrigerant circuits (tem
perature/pressure ranges:
NT
- low-pressure normal-temperature refrigeration,
LT
- low-pressure low-tempera
ture refrigeration and
HP
- high pressure) Depending on the expansion stage, the maximum number of relay/
control stages is as follows:
‐ 4 relay/control stages
(basic configuration)
‐ 8 relay/control stages
(first expansion stage)
‐ 12 relay/control stages
(second expansion stage)
The relay/control stages can be allocated to one control loop or split between the two control loops. Capacity-
controlled compressors with up to three capacity stages are supported.
S
The following control types are supported:
- Step control
- Speed control
- Combined control
S
Base load rotation (running sequence control)
S
Load shedding
S
Booster operation
S
Data archiving
- Messages/alarms
- Starts
- Run times
- Activity/utilization
S
Monitoring functions
Summary of Contents for VS 300
Page 8: ...vi Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 18: ...System Design of VS 300 10 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 22: ...Application of VS 300 14 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 160: ...Decommissioning and disposal 152 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 166: ...Alarms and Messages of VS 300 158 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...
Page 170: ...162 Doku Version 2 05 Firmware 2 10 15 September 2017 Notice ...