5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
147
121
(79h)
Param_common_
operation_modes
G/S
BYTE
Bit 3 - Configuration check
Bus or slave-oriented configuration check
(without function if MC = 1)
0: Bus-oriented:
If the PLC configuration check is activated,
data exchange is only started if the configu-
ration stored in the XNE-1SWIRE fully
matches the SET configuration stored in the
PLC. Modifying the bus during operation
causes the system to be aborted.
1: Slave oriented:
If the PLC configuration check is activated,
data exchange is started with all SWIRE
slaves that match the SET configuration
stored in the PLC. The SWIRE slaves that do
not match the SET configuration stored in
the PLC do not perform any data exchange.
Bit 4 - Moeller conformance
(from version VN 01-04)
Behacior of the XNE-1SWIRE in accordance
with SWIRE Comformance criteria.
0: Default behavior
1: The XNE-1SWIRE master responds
according to the Moeller SWIRE Confor-
mance criteria.
Bit 5 to bit 6: reserved
Table 61:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description