5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
78
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
Object instance 2
Table 40:
Object instance
2, Gateway
Instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
109
(6Dh)
Status register 2
G
STRUCT
Gateway-Status contains general gateway
status information:
Gateway
– Bit 15: "I/O Controller Error" The communi-
cation controller for the I/O-system is
faulty.
– Bit 14: "Force Mode Active Error" The
Force Mode is activated.
– Bit 13: reserved
– Bit 12: reserved
Module bus
– Bit 11: "I/O Cfg Modified Error" The I/O-
configuration has been changed and is
now incompatible.
– Bit 10: "I/O Communication Lost Error" No
communication on the I/O module bus.
Voltage errors
– Bit 09: "U
SYS
too low" System supply
voltage too low (< 18 VDC).
– Bit 08: "U
SYS
too high" System supply
voltage too high (> 30 VDC).
– Bit 07: "U
L
too low" Load voltage too low (<
18 VDC).
– Bit 06: "U
L
too high" Load voltage too high
(> 30 VDC)
– Bit 05: "I
SYS
too high" Overload of the
system voltage supply.
– Bit 04: reserved
Warnings
– Bit 03: "I/O Cfg Modified Warning"
– Bit 02: reserved
– Bit 01: reserved
– Bit 00: "I/O Diags Active Warning" At least
one I/O-module sends active diagnostics.