5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
145
118
(76h)
Diag_config_error G
WORD
One bit per SWIRE slave shows the config-
uration state of the slave:
Slave 1 belongs to bit 0,
slave 2 to bit 1 etc.
0: The physical structure of the SWIRE bus
was accepted and the SWIRE bus is in oper-
ation.
1: The physical structure of the SWIRE bus
does not match the configuration stored in
the XNE-1SWIRE. The physical structure
was not accepted The SWIRE bus does not
start operation (SW LED flashing).
119
(77h)
Diag_communica
tion_error
G
WORD
One bit per SWIRE slave shows possible
communication errors.
Slave 1 belongs to bit 0,
slave 2 to bit 1 etc.
0: No error present.
1: A communication error is present, such
as a slave is no longer reached, its internal
timeout has elapsed or communication is
faulty. The master cannot carry out data
exchange with at least one slave.
120
(78h)
Diag_PKZ_error
G
WORD
One bit per SWIRE slave shows if the PKZ
has tripped or not:
Slave 1 belongs to bit 0,
slave 2 to bit 1 etc.
0: No PKZ (overcurrent protective circuit-
breaker) has tripped or diagnostics function
has been deactivated via the parameter
setting.
1: At least one PKZ (overcurrent protective
circuit-breaker) has tripped.
Table 61:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description