5 Implementation of EtherNet/IP
5.3 VSC-Vendor Specific Classes
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
103
5.3.13
Analog input THERMO module class (VSC111)
This Class contains all information and parameters for analog input modules for thermo-
couples.
Class instance
Object instance
Note
Please refer to Chapter 5.3.1 Class instance of the VSC, Page 76, for the description
of the class instances for VSC.
Table 54:
Object instance
Attr.
no.
dec.
(hex.)
Attribute name
G
et/
S
et
Type
Description
100
(64h)
Max object attri-
bute
G
USINT
Contains the number of the last object attri-
bute to be implemented.
101
(65h)
Module present
G
BOOL
0 = module missing, base module without
electronic module.
1 = module is plugged
102
(66h)
Terminal slot
number
G
USINT
The slot number of the base module
belonging to the module (base module to
the right of the gateway = No. 1).
Corresponds to the respective Instance
Number within the TERMINAL SLOT
CLASS.
103
(67h)
Module ID
G
DWORD
Contains the module ID.
104
(68h)
Module order
number
G
UDINT
Contains the ident number of the module.
105
(69h)
Module order
name
G
SHORT
STRING
Contains the name of the module, for
example, "XN-2AI-THERMO-PI".
106
(6Ah)
Module revision
G
USINT
Contains the revision number of the module
firmware.
107
(6Bh)
Module type ID
G
ENUM
USINT
Describes the module type: see attribute
107 (6Bh) on page 86
108
(6Ch)
Module
command inter-
face
G/S
ARRAY
The control interface of the XI/ON module.
ARRAY OF:
BYTE: Control byte sequence
109
(6Dh
Module response
interface
G
ARRAY
Response interface of the XI/ON module.
ARRAY OF:
BYTE: Response byte sequence