4 Technical features
4.7 Status indicators/diagnostic messages gateway
XI/ON: XNE-GWBR-2ETH-IP
09/2011 MN05002007Z-EN
www.eaton.com
49
IOs
Off
CPU not supplied.
– Check the voltage supply U
SYS
at
the gateway.
Green
The configured module bus
station corresponds to the physi-
cally connected station, communi-
cation is active.
-
Green
flashing
1 Hz
Station is in the I/O-ASSISTANT
Force Mode.
– Deactivate the I/O-ASSISTANT
Force Mode.
Red
CPU is not ready, V
CC
level is not
within the required range
→
possible reasons:
– too many modules connected to
the gateway
– short circuit in connected
module
– hardware error in gateway
– Check wiring at the gateway and
the voltage supply.
– Dismount modules
– Replace the gateway.
Red
flashing,
1 Hz
Non-adaptable modification of the
physically connected station.
– Compare the planned XI/ON
station with the physical station.
– Check the physical XI/ON station
for defective or incorrectly fitted
electronics modules.
Red
flashing,
4 Hz
No module bus communication
– At least one electronics module
has to be mounted correctly and
has to be able to communicate
with the gateway.
Red/green
flashing,
1 Hz
Adaptable modification of the
actual layout of the module bus
participants; data transfer possible
– Check the XI/ON station for
missing or new, unplanned
modules.
MS
Off
XI/ON station not supplied.
– Check the voltage supply at the
gateway.
Green
Displays an active CIP Class 1
I/O connection
–
Green
flashing
Gateway is ready for operation
–
Red
Gateway indicates error
–
Red
flashing
DHCP/BootP search of settings,
wait for address setting
–
Table 7:
LED-displays
LED
Status
Meaning
Remedy