CHAPTER 8 - PXG600E CONFIGURATION WEB PAGE
EATON
PXG600E User Manual • IM02603003E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
54
Example A - Single Main / Single Bus System
1.
System plan
- This system is a single lineup of LV switch gear. It has a
single incoming Main from the utility that has an Eaton Digitrip 1150
breaker / trip unit at INCOM address x01. The current capacity of the
Main feed is 1000A.
There are four feeder circuits connected to the power Bus coming from
the Main. Each of these circuits is protected by an Eaton Optim 550 at
INCOM address 02 through 05. Each feeder circuit has a capacity of
100A. The feeder circuits are to be labeled Feeder 1-4.
The following are some of the optional settings that can be made as
devices are added to the system. In this example we are adding Eaton
Optim 550 devices:
•
Enable trending
•
Enable device
•
Disable all polling, trending and events for individual parameters
•
Set Low and High events for Ia, Ib and Ic
•
Set priorities for user and / or native events
•
Enable actual, average, minimum and / or maximum interval logs
•
Configure email feature to send email when an event occurs and
when the event clears
The system is depicted in
Figure 45
.
Figure 45
Capacity - 1000A
Digitrip 1150
INCOM Addr01
LV Source
Capacity - 100A
Optim 550
INCOM Addr02
Feeder 1
Capacity - 100A
Optim 550
INCOM Addr03
Feeder 2
Capacity - 100A
Optim 550
INCOM Addr04
Feeder 3
Capacity - 100A
Optim 550
INCOM Addr05
Feeder 4