CHAPTER 4 - PXG600E OVERVIEW
11
EATON
PXG600E User Manual • IM02603003E
Rev 5, 11-May-2012 • Firmware Version 5.03:3835
Chapter 4
PXG600E Overview
Layout of PXG600E
Figure 2
NOTICE:
Figure 2
is a typical example of the PXG600E. Your
equipment may differ.
A.
VDC – Power Input - Connect to an external DC power supply that meets UL
508/1131 Class 2 standards. The supply must be capable of sourcing
24 VDC +/- 20% at 0.8 A.
B.
COM2B - RS-232 port used to connect to Modbus RTU devices. COM2A and
COM2B are software selectable - cannot use both at same time.
C.
COM2A - RS-485 port for connection to either QCPort or Modbus RTU devices.
COM2A and COM2B are software selectable - cannot use both at same time.
D.
COM1- RS-485 port for connection to either QCPort or Modbus RTU devices.
E.
INCOM, used to connect to INCOM devices.
F. / G.
Upstream/Downstream ethernet port connections; can be daisy-chained –
Connect to Local Area Network (LAN) using CAT 5 or better cable.
See
“Connecting a PXG600E to the Ethernet LAN” on page 16.
H.
USB Configuration Port.
I. / J. / K. / L.
COM1 / INCOM / COM2A / COM2B traffic indicator. If indicator does not blink it
means that no devices have been entered into the PXG600E device list for this
port. If indicator blinks green it means that devices entered into the PXG600E
device list are connected, but not responding, or the physical connection is
intermittent. If indicator blinks yellow / red it means that devices entered into
the PXG600E device list are responding.
M.
Power Indicator (ON condition is Green).
N.
Restart button. This button has multiple functions:
•
If the button is pressed for less than 3 seconds, the PXG will perform a reboot - press
F5 on your computer keypad to refresh the screen.
•
If the button is pressed for at least 3 seconds but less than 10 seconds, the network
settings and passwords will be reset to their defaults.
•
If the button is pressed for 15 seconds or longer, all your settings will be reset to the
default and the log files will be cleared. If you personalized the image in the banner
at the top of the PXG web page, it will return to the default image. Ensure that you
have saved your configuration, using the
Save and Restore on
page 109
function,
BEFORE
you continue.
COM 1
INCOM
COM 1
REST
AR
T
SHLD
D2
D1
CMN
A (-)
B (+)
+ V
GND
1 2
PXG 600E
24 VDC
PXG600E_001
UPSTREAM
DOWNSTREAM
D
E
F
G
H
M
COM 2
A
B
CMN
A (-)
B (+)
COM 2
B
A
INCOM
I
J
K
L
N
B
C
A