The UPS system can be further enhanced by adding optional accessories such as a Remote Emergency Power-
off (REPO) control, RMP II, SCM II, RIM II, or X-Slot communication cards. See
Installing Options and Accessories
for additional information.
•
Remote Monitor Panel II (RMP II)
– An optional RMP II contains backlit status indicators and a local horn,
allowing monitoring of the operational status and alarm condition of the UPS from virtually any location
within the facility.
•
Relay Interface Module II (RIM II)
– An optional RIM II uses relay contact closures to indicate the UPS
operating status and alarm condition.
•
Supervisory Contact Module II (SCM II)
– An optional SCM II establishes an interface between the UPS
system equipment and the customer's monitor.
•
X-Slot Cards
– Optional X-Slot cards support several protocols, such as SNMP, HTTP, IBM AS/400, and
Modbus.
•
PredictPulse™ Remote Monitoring and Management Service
– PredictPulse is a subscription
monitoring and management service from Eaton that collects and analyzes data from connected power
infrastructure devices, providing us with the insight needed to make recommendations and take action on
your behalf. It’s also powered by CA Technologies, bringing together the best in hardware and software.
Like a second set of eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of
alarms and system performance (load, temperature/humidity, battery health, energy savings and service
level) to reduce downtime risk and expedite repairs. PredictPulse also shares real-time status and trend
information via an online dashboard and smartphone mobile app (Apple and Android), giving subscribers
insights about past and current performance, a list of all active alarms, and asset management data (i.e.,
battery date codes, last and next scheduled service dates, firmware versions). The service notifies
customers of critical alarms, supports remote diagnostics, and facilitates smart dispatch of technicians.
PredictPulse requires a Power Xpert
®
Gateway Card (PXGX) connectivity card in an X-Slot communication
bay and an Environmental Monitoring Probe (EMP) for battery temperature/humidity monitoring.
See
for additional information on monitoring and communication features.
11..55
B
Baatttteerryy S
Syysstteem
m
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead-acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPSs in distributed bypass and parallel systems must use a separate battery system.
Consult the
Eaton
®
Power Xpert
®
9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR)
Installation Manual (P-164000580)
for specifics on battery cabinet usage with the 9395P-600.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
NOTE
The 9395P-600 system can trip a maximum of six battery cabinets total. This applies to
both the 1085 standard and High Rate series batteries. If more than six battery cabinets
in total are needed in a separate UPM battery configuration, DO NOT hook up the shunt
trips.