Bypass and output overcurrent protection and bypass and output disconnect switches are to be provided by
the customer. Module Output Breakers (MOBs) are to be provided by the customer.
lists the recommended rating for 600V, 575V, 480V, 415V, 400V, and 380V bypass, output, and MOB
circuit breakers with 100% breaker rating. Bypass breakers are not applicable for IOM configurations.
Table 30. Recommended Bypass, Output, and MOB Circuit Breaker Ratings (100% and 80%)
UPS Model
Output kW/kVA
Input Rating
%
600V
575V
480V
415V
400V
380V
Eaton 9395P-600/600
100
N/A
N/A
800A
N/A
N/A
N/A
80
N/A
N/A
1000A
N/A
N/A
N/A
Eaton 9395P-600/550
100
600A
600A
700A
800A
800A
1000A
80
700A
700A
1000A
1000A
1000A
1200A
Eaton 9395P-600/500
100
500A
600A
700A
700A
800A
800A
80
700A
700A
800A
1000A
1000A
1000A
Eaton 9395P-600/450
100
450A
500A
600A
700A
700A
700A
80
600A
600A
700A
800A
1000A
1000A
Eaton 9395P-600/400
100
400A
450A
500A
600A
600A
700A
80
500A
600A
600A
700A
800A
800A
Eaton 9395P-600/300
100
300A
350A
400A
450A
450A
500A
80
400A
400A
500A
600A
600A
600A
Eaton 9395P-600/275
100
300A
300A
350A
400A
400A
450A
80
350A
350A
450A
500A
500A
600A
Eaton 9395P-600/250
100
250A
300A
350A
350A
400A
400A
80
350A
350A
400A
450A
500A
500A
Eaton 9395P-600/225
100
250A
250A
300A
350A
350A
350A
80
300A
300A
350A
400A
450A
450A
Eaton 9395P-600/200
100
200A
250A
300A
300A
300A
350A
80
250A
300A
350A
350A
400A
400A
NOTE Bypass conduit data is not applicable to IOM configurations.
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required by NEC or local codes.
The battery disconnect switch should be installed between the battery and the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of
nominal DC voltage at rated battery current.
External DC input overcurrent protection and disconnect switch is to be provided by the customer.