Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
53
Table 25. 480V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit Trade
Size
Number of
Conduits
Eaton 9395P-600/600
Eaton 9395P-600/550
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
Eaton 9395P-600/500
Eaton 9395P-600/450
Eaton 9395P-600/400
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
3
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
Eaton 9395P-600/300
Eaton 9395P-600/275
Eaton 9395P-600/250
Eaton 9395P-600/225
Eaton 9395P-600/200
See Note
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2.5
4
AC Input to Bypass and Output
(A, B, C, Ground)
4
2.5
3
DC
(Common
Battery)
Battery
(Positive, Negative, Ground)
7
4
2
All models
DC
(Separate
Battery - per
UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
: Refer to the notes at the bottom of
Input/Output Ratings and External Wiring Requirements.