Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
81
6.
If installing a UPS configured as an Input Output Module (IOM), proceed to Step 8; otherwise, proceed to
Step 7.
7.
Using hardware from the external wiring terminal hardware kit (see
), connect phase A, B, and C
bypass input power wiring from the utility source to the bypass input terminals in the ISBM section. See
paragraph
UPS System Power Wiring Preparation
for wiring and termination requirements.
8.
If wiring a distributed bypass system, proceed to Step 9; otherwise, proceed to Step 11.
9.
Using hardware from the external wiring terminal hardware kit (see ), connect phase A, B, and C wiring
from the output terminals of each UPS unit to the customer-supplied tie cabinet or load distribution panel.
See paragraph
UPS System Power Wiring Preparation
for wiring and termination requirements.
10. Proceed to paragraph
.
11. Using hardware from the external wiring terminal hardware kit (see
), connect phase A, B, and C
power wiring from output terminals to the critical load. See paragraph
UPS System Power Wiring Preparation
for wiring and termination requirements.
12. Proceed to paragraph
.
Summary of Contents for Power Xpert 9395P-600/600