9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
Table 24. 575V Power Cable Conduit Recommendations
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
Eaton 9395P-600/550
575 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2 or 3
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
2 or 3
Eaton 9395P-600/500
575 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2 or 3
AC Input to Bypass and Output
(A, B, C, Ground)
4
2
2 or 3
Eaton 9395P-600/450
575 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2 or 3
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
2 or 3
Eaton 9395P-600/400
575 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2 or 3
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
2 or 3
Eaton 9395P-600/300
575 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
2 or 3
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
2 or 3
DC (same for all ratings)
Battery (Positive, Negative, Ground)
See Note 1
NOTE 1 Select conduit taking into consideration the DC input wire sizes and terminations listed in appropriate Tables, type of battery
installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).
NOTE 2 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
: Refer to the notes at the bottom of
Input/Output Ratings and External Wiring Requirements.