72
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
Figure 23. ISBM Section to UPM Section Joining Brackets
Front View Base Bracket
UPM Section Base
ISBM Section Base
Bracket from Kit
Screw from Kit
Screw from Kit
Top View Rear Bracket
UPM
Section Top
ISBM
Section Top
Screw from Kit
Screw from Kit
Bracket from Kit
Back
Top View Front Bracket
UPM
Section Top
Screw from Kit
Screw from Kit
ISBM
Section Top
Bracket from Kit
Front
44..44
EElleeccttrriiccaallllyy C
Coonnnneeccttiinngg tthhee S
Seeccttiioonnss ((660000V
V M
Mooddeellss O
Onnllyy))
NOTE
AC and DC input intercabinet power wiring harnesses are supplied coiled and secured in
the UPM wireway on the left side of the UPM section (see
1.
Align the ISBM and UPM sections in their final installation locations.
2.
Remove the ISBM doors and optional dead fronts.
3.
Remove the UPM section cover to gain access to UPM power wires.
4.
Locate the AC and DC input inter-cabinet power wiring harnesses (long cables labeled xG1, xG2, xG3, xG4,
and xG5). Remove wire ties as necessary and uncoil the cables.
5.
Locate the inter-cabinet wiring terminal hardware kit packed on the bottom right side of the ISBM section.
6.
Locate the wires labeled 1G3 and 2G3 for the UPM battery input.
7.
Route the wires labeled 1G3 and 2G3 through the transformer section into the I/O section and land on bus
bars E4 and E5 (DC+ and DC-). See
.
Summary of Contents for Power Xpert 9395P-600/600