9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
1
C
Chhaapptteerr 11 IInnttrroodduuccttiioonn
The Eaton
®
Power Xpert
®
9395P-600 uninterruptible power supply (UPS) is a true online, continuous-duty,
transformerless, double-conversion, solid-state, three-phase system, providing conditioned and uninterruptible
AC power to protect the customer's load from power failures.
The 9395P-600 UPS online power protection system is used to prevent loss of valuable electronic information,
minimize equipment downtime, and minimize the adverse effect on production equipment due to unexpected
power problems.
The 9395P-600 UPS system continually monitors incoming electrical power and removes the surges, spikes,
sags, and other irregularities that are inherent in commercial utility power. Working with a building's electrical
system, the UPS system supplies clean, consistent power that sensitive electronic equipment requires for
reliable operation. During brownouts, blackouts, and other power interruptions, batteries provide emergency
power to safeguard operation.
The UPS is available as a single unit or an optional multiple unit distributed bypass system (see paragraph
). The UPS is housed in a free-standing cabinets.
Four 9395P-600 UPS system configurations are available for 480V, 415V, 400V, and 380V models:
•
two standard UPM configurations with one or two UPMs (see
•
two optional configurations with a field installed UPM (FI-UPM) added to the left of a standard
configuration (see
NOTE
The FI-UPM is not supplied as standard, but is available as an option to provide
upgradability to a maximum of 600 kVA. Adding the FI-UPM can also provide N+1
redundancy if the power requirements are less than the single UPM rating. The FI-UPM
matches the UPS in style and color.
Four 9395P-600 UPS system configurations are available for 600V models:
•
two 600V UPM configurations with one or two UPMs (see
•
two optional 600V configurations with a field installed UPM (FI-UPM) added to the left of a 600V
configuration (see
11..11
S
Siinnggllee U
UP
PM
M aanndd TTw
woo U
UP
PM
M C
Coonnffiigguurraattiioonnss
The standard Single UPM 9395P-600 UPS configuration contains two sections:
•
an ISBM section configured either as an integrated system bypass module (ISBM) or an input output
module (IOM) rated for a maximum of 600 kVA
•
a UPM section with one factory installed UPM
The standard Two UPM UPS 9395P-600 configuration has two sections:
•
an ISBM section configured either as an integrated system bypass module (ISBM) or an input output
module (IOM) rated for a maximum of 600 kVA
•
a UPM section with two UPMs
For all models except the 600V, the two sections are shipped as a joined unit on the same pallet (see
).
For the 600V Single and Two UPM configurations, the ISBM section and the UPM section are shipped
separately on different pallets (see
).
NOTE
Note that the ISBM section for the 600V models differs from the ISBM section for the
other models.