Installing Options and Accessories
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
5-5
Figure 5-3. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
Figure 5-4. Distributed Bypass System UPS CAN Wiring without MOBs
UPS 1
UPS 2
UPS 3
UPS 4
CAN
(If Installed)
(If Installed)
Pull Chain
NOTE
This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Shielded Twisted Pair
Shielded Twisted Pair
Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
UPS 2
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
NOTE
External CAN connections between UPSs require shielded twisted-pair wire.
Table 5-2. CAN Bridge Card Wiring Terminations
From
UPS 1 CAN Bridge Card
To
UPS 2 CAN Bridge Card
To
UPS 3 CAN Bridge Card
(If Installed)
To
UPS 4 CAN Bridge Card
(If Installed)
J3
8 (L)
J3
8 (L)
J3
8 (L)
J3
8 (L)
J3
9 (H)
J3
9 (H)
J3
9 (H)
J3
9 (H)
J3
10 (Shield)
J3
10 (Shield)
J3
10 (Shield)
J3
10 (Shield)