UPS Installation Plan and Unpacking
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
3-19
AC Output to Critical Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Common
Battery
E4
Battery (+)
8 – 2 bolt mounting (2 UPM)
12 – 2 bolt mounting (3 UPM)
16 – 2 bolt mounting (4 UPM)
76 (56)
M12
E5
Battery (-)
8 – 2 bolt mounting (2 UPM)
12 – 2 bolt mounting (3 UPM)
16 – 2 bolt mounting (4 UPM)
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI-UPM)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral
12 – 2 bolt mounting
22 (16)
M10
Customer Ground
Ground
Ground
15 – 1 bolt mounting
22 (16)
M10
NOTE
V
NOTE
V
Bypass terminations are not applicable to IOM configurations.
Table 3-12. UPS External Power Cable Terminations for the Three UPM Power Xpert 9395-825/650, 9395-825/750, and 9395-825/825 and the
Two UPM Power Xpert 9395-825/450, 9395-825/500, 9395-825/550
Terminal Function
Terminal
Function
Bus Landings
Tightening Torque
Nm (lb ft)
Bolt Size
Table 3-13. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 25 mm
15
Ground
180190078-087
Bolt, Grade 5
M12 x 45 mm
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180190078-113
Flat Washer
M10
15
Ground
180500036-100
Flat Washer
M12
184
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500036-120
Conical Washer
M10
15
Ground
180500037-100
Conical Washer
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500037-120
Nut
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.