UPS Operating Instructions
7-10
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
Figure 7-6. Typical System Status Screen
MAINTENANCE BYPASS
BYPASS
UPM: OFFLINE
SHUTDOWN
:
AVAILABLE
:
OFF
:
SYSTEM STATUS
CONTROL
S
ESC
F
F
O
R
E
G
R
A
H
C
:
UPS
Table 7-4. Typical System Status Messages
Function
Message
UPS
Shutdown; Bypass; Online; Online with ESS; VMMS; High
Alert
Bypass
Off; On; Available
Maintenance Bypass
Off; On
Charger
Charger Off; Charging
UPM (during startup)
DC Starting, Charger Off; DC Starting, Close Battery Breaker;
Inverter Starting; Inverter Syncing; Ready; Online
UPM 1
UPM 4 (if FI-UPM is installed)
Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online,
Charger Off; Online, Charging
Table 7-5. Command Menu Operation
Function
Subfunction
Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired, then
press the
SELECT
pushbutton to execute the command or proceed to further command
screens.
Go to Online
Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass mode.
Enable (Disable) Energy Saver
Enables or disables Energy Saver System mode. Enable changes to Disable when the
Energy Saver System mode is enabled.
Enable (Disable) Var Module Management
Enables or disables the Variable Module Management System mode. Enable changes to
Disable when the Variable Module Management System mode is enabled.
Start High Alert
Starts High Alert mode.
Go to Bypass
Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online mode.
Load Off