9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
10-1
Chapter 10 Product Specifications
10.1
Model Numbers
The UPS is housed in a free–standing cabinet with safety shields behind the door and front panels. The UPS is
available in 50 or 60 Hz with various output power ratings.
10.2
Specifications
The following sections detail the input, output, battery, and environmental specifications for the UPS.
10.2.1 UPS Input
Models
Power Rating
Frequency
Power Xpert 9395-825/650 (three UPM)
650 kVA
50/60 Hz
Power Xpert 9395-825/750 (three UPM)
750 kVA
50/60 Hz
Power Xpert 9395-825/825 (three UPM)
825 kVA
50/60 Hz
Power Xpert 9395-825/450 (two UPM)
450 kVA
50/60 Hz
Power Xpert 9395-825/500 (two UPM)
500 kVA
50/60 Hz
Power Xpert 9395-825/550 (two UPM)
550 kVA
50/60 Hz
Operating Input Voltage
400 Vac
480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3-4, Table 3-5, Table 3-6, Table 3-7, or Table 3-8.
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801
4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load
Battery Shunt Trip
48 Vdc