UPS Installation Plan and Unpacking
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
3-21
Table 3-16. Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of Wires in
Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Power Xpert 9395-825/650
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
3
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
4
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
3
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
2-1/2
3
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
4
Power Xpert 9395-825/750
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
3
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
4
Power Xpert 9395-825/825
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5