Figure 33. Many Bubbles-Inline Sight Glass
6.
When suction pressure reaches 120 psig
, observe the
INLINE
sight glass. If it is
either clear as shown in Figure 34, or has a trickle of bubbles as shown in Figure 35,
no additional refrigerant charge is required. Go to step 10.
Figure 34. Clear-Inline Sight Glass
Figure 35. Trickle of Bubbles-Inline Sight Glass
7.
When suction pressure is 120 psig, there are still many bubbles in the INLINE
sight glass
, as shown in Figure 33, refrigerant must be added to the system through
the final charging port.
8.
Observe the refrigerant flow in the INLINE sight glass.
If the sight glass has
cleared, as shown in Figure 34, or there is a trickle of bubbles as shown in Figure 35,
the system is fully charged.
IMPORTANT!
Add refrigerant SLOWLY to the system through the final charging port.
Add no more than 8 ounces of refrigerant at a time and wait 10 minutes,
observing the INLINE sight glass to determine the refrigerant status,
before adding more refrigerant.
Summary of Contents for AVS-0030-A
Page 15: ...SD 410 QS H 06 15 Page 15 Figure 8a SD H Compressor Unit Electrical Ladder Diagram 230 1 60...
Page 16: ...SD 410 QS H 06 15 Page 16 Figure 8b SD H Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 17: ...SD 410 QS H 06 15 Page 17 Figure 9a SD H Compressor Unit Electrical Ladder Diagram 230 3 60...
Page 18: ...SD 410 QS H 06 15 Page 18 Figure 9b SD H Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 29: ...SD 410 QS H 06 15 Page 29 Figure 15 Disassembled Plug Connector...
Page 49: ...SD 410 QS H 06 15 Page 49 Figure 38 Cooling Mode Start Up...
Page 58: ...SD 410 QS H 06 15 Page 58...
Page 59: ...SD 410 QS H 06 15 Page 59...
Page 60: ...SD 410 QS H 06 15 Page 60...
Page 61: ...SD 410 QS H 06 15 Page 61...
Page 62: ...SD 410 QS H 06 15 Page 62...
Page 63: ...SD 410 QS H 06 15 Page 63...