Plumbing
A typical primary hydronic plumbing circuit for an SD(H) system is illustrated in Figure 11.
Figure 11. Typical SD(H) Primary Hydronic Circuit Plumbing
The components are as follows:
1.
Flowmeter
: Model ETI-A1-116000-1 hydronic water/antifreeze solution flowmeter is available
from ETI and is field calibrated for the specific antifreeze mixture. The kit includes calibration
equipment.
2.
Strainer:
Models ST-1836 (for 1.5 thru 3.0 ton systems) and ST-4272 (for 3.5 thru 6.0 ton
systems) are 20 mesh, brass, inline strainers, available from ETI and necessary to trap
particles and maintain proper flow through the brazed plate heat exchanger channels.
3.
Temperature Controller:
Model HHK-1872 is a hydronic heating controller. This controller
can be mounted remotely and come with a capillary tube 6 feet long, thermal bulb, thermal
paste and the NPT thermal well insert and are available from ETI.
Summary of Contents for AVS-0030-A
Page 15: ...SD 410 QS H 06 15 Page 15 Figure 8a SD H Compressor Unit Electrical Ladder Diagram 230 1 60...
Page 16: ...SD 410 QS H 06 15 Page 16 Figure 8b SD H Compressor Unit Electrical Schematic Diagram 230 1 60...
Page 17: ...SD 410 QS H 06 15 Page 17 Figure 9a SD H Compressor Unit Electrical Ladder Diagram 230 3 60...
Page 18: ...SD 410 QS H 06 15 Page 18 Figure 9b SD H Compressor Unit Electrical Schematic Diagram 230 3 60...
Page 29: ...SD 410 QS H 06 15 Page 29 Figure 15 Disassembled Plug Connector...
Page 49: ...SD 410 QS H 06 15 Page 49 Figure 38 Cooling Mode Start Up...
Page 58: ...SD 410 QS H 06 15 Page 58...
Page 59: ...SD 410 QS H 06 15 Page 59...
Page 60: ...SD 410 QS H 06 15 Page 60...
Page 61: ...SD 410 QS H 06 15 Page 61...
Page 62: ...SD 410 QS H 06 15 Page 62...
Page 63: ...SD 410 QS H 06 15 Page 63...