Connecting an Access Manager or RF Net Manager
39
ENiQ/ELS/DOM Tapkey ACM, potential-free changeover contact, control unit
outputs
Electric strength
30 V DC
125 V AC
Current carrying capacity
1 A/DC
0.3 A/AC
Only attach external components, e. g. actuators, which are suitable for this.
The manufacturer will not be held liable for any damage which results from the
use of unsuitable external components.
Removing terminals from the device
Pull the pluggable terminals away
from the back of the device
carefully.
Loosen the screws on the
terminal if necessary.
Remove around 40 mm of the
insulation of the cable sheath.
Remove around 5 mm of the
insulation of the individual wires.
Attach suitable wire end ferrules
if necessary.
You can connect the connection
cables according to the
corresponding wiring diagram. You
can find the diagram for your device
on the following pages.
Making connections
Perform the connection of the devices in the following order:
Connect devices together (HiSec)
Connect network
Connect power supply
Check