15
Table 7: Airflow Data, models with 1/2 HP, ECM motors
SW1- HEAT
DIP switch position
HEAT INPUT
(USGPH)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
0,68
1160
1310
990
B
(1=ON, 2=OFF)
0,80
1340
1400
1140
C
(1=OFF, 2=ON)*
0,68
1000
1130
850
D
(1=ON, 2=ON)*
0,80
1160
1310
990
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
3,5
1050
1210
895
B
(1=ON, 2=OFF)
3,0
900
1035
765
C
(1=OFF, 2=ON)
2,5
750
865
640
D
(1=ON, 2=ON)
2,0
600
690
510
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with SW3-ADJ
DIP switch position A
CFM with SW3-ADJ
DIP switch position B
CFM with SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
3,5
1400
1400
1260
B
(1=ON, 2=OFF)
3,0
1200
1320
1080
C
(1=OFF, 2=ON)
2,5
1000
1100
900
D
(1=ON, 2=ON)
2,0
800
880
720
SW4- DEALY
DIP switch position
HEAT INPUT
(USGPH)
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
A
(1=OFF, 2=OFF)
0,68
13% - 45 sec.
19% - 60 sec
38% - 3 min.
B
(1=ON, 2=OFF)
0,80
13% - 45 sec.
19% - 30 sec
38% - 3 min.
C
(1=OFF, 2=ON)
All
13% - 45 sec.
100% - 0 sec
100% - 2 min.
D
(1=ON, 2=ON)
All
13% - 90 sec.
100% - 0 sec
100% - 2 min.
No adjustment
required
A/C size
PreRun On-Delay
CFM Level - Time
ShortRun On-Delay
CFM Level - Time
Off-Delay
CFM Level - Time
-
All
NO DELAY
NO DELAY
100% - 90 sec
* Alternate adjustment in oil-fired heating mode with higher temperature rise
CONTINUOUS FAN
24 VAC input (R) on G only
COOLING OR HEAT PUMP HEATING MODE
24 VAC input (R) to G, Y/Y2 and O (for cooling)
In Cooling - Dehumidification mode, with no 24 VAC input to DH, the CFMs are reduced by 15%.
The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 (first stage cooling mode)
OIL HEATING MODE
24 VAC input (R) on W only
DELAY PROFILE FOR COOLING OR HEAT PUMP HEATING MODE
DELAY PROFILE FOR OIL HEATING MODE
air distribution system.
PreRun and ShortRun are the periods of time when the the blower starts at very low CFM to minimize the
distributon of cool air in the system and then runs up to normal speed.
Off Delay is the time required to cool down the heat exchanger with low CFMs, to minimize cool draft in the
Summary of Contents for AMP112SD
Page 17: ...17 Figure 9 Furnace Dimensions...
Page 18: ...18 Figure 10 Wiring Diagram 4 Speed Motor PSC...
Page 19: ...19 Figure 11 Wiring Diagram Variable Speed Motor ECM...
Page 20: ...20 Figure 12 Parts list with 4 speed motor PSC B50091C...
Page 22: ...22 Figure 13 Parts list with variable speed motor ECM B50092C...
Page 25: ......
Page 42: ...19 Figure 9 Dimensions de la fournaise...
Page 43: ...20 Figure 10 Diagramme lectrique avec moteur 4 vitesses PSC...
Page 44: ...21 Figure 11 Diagramme lectrique avec moteur vitesse variable ECM...
Page 45: ...22 B50091C Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...
Page 47: ...24 B50092C Figure 13 Liste de pi ces avec moteur vitesse variable ECM...