10
simultaneous operation of the furnace and the heat pump. It
also prevents a direct transition from heating by way of the
heat pump to heating with oil. Refer to the thermostat
instructions or those of another control used for the proper
wiring.
If a coil blower compartment is used, install air tight, motorized
and automatic air dampers. Cold air coming from the coil and
passing across the furnace can cause condensation and
shorten the life of the heat exchanger.
3 OPERATION
3.1 START-UP
Before starting up the unit, be sure to check that the following
items are in compliance:
1.
The electrical installation, the oil supply system, the
venting system, combustion air supply and ventilation;
2.
The blower access door is in place and the blower rail
locking screws are well tightened;
3.
The Blocked Vent Shut-Off (BVSO) is installed according
to instructions (for chimney venting);
4.
The oil supply valve is open;
5.
The burner ‘’Reset’’ button is well pushed in or re-armed;
6.
The preliminary air adjustments on the burner
comply
with the technical specifications in this manual;
7.
The blower speed adjustments for heating and air
conditioning are appropriate and according to the
specifications in this manual;
8.
The blower start/stop delays are satisfactory;
9.
The thermostat of the room is in the heating mode and is
set higher than the ambient temperature.
To start the unit, turn the main electrical switch on.
3.2 OPERATING
SEQUENCE
OIL
HEATING
MODE
1.
The W-R contact closes;
2.
The burner motor starts up to pre-purge the combustion
chamber for a period of 10 to 15 seconds. During that time
a spark is established on the electrodes;
3.
The solenoid valve opens and a flame is established.
Shortly after, the electrodes cease to spark;
4.
Then the blower runs up to full speed. The delay depends
on the adjustments that were made on the electronic
board, which controls the blower motor. Refer to Sections
2.11 and 2.12, as well as the CFM table for more details.
5.
When the call for heat is satisfied, the solenoid valve
closes, the flame goes out and the burner motor stops
(after post purge delay, if applicable).
6.
The blower stops shortly after the burner. The delay
depends on the adjustments that were made on the
electronic board that controls the blower. Refer to
Sections 2.11 and 2.12, as well as the CFM table for more
details.
Note: A detailed operating sequence of the oil burner is
outlined in the instructions provided with the burner.
3.3 CHECKS
AND
ADJUSTMENTS
3.3.1
Purging The Oil Line
Open the bleed port screw and start the burner. Allow the
oil to drain into a container for at least 10 seconds. The oil
should flow absolutely free of white streaks or air bubbles
to indicate that no air is being drawn into the suction side
of the oil piping and pump. Slowly close and tighten the
bleed screw. Once closed, the flame will light up.
3.3.2 Pressure
Adjustment
The oil pressure must be adjusted according to the
Technical Specifications of this manual. An adjustment
screw and a connection for a pressure gauge are located
on the oil pump for that purpose. Also refer to the burner
instruction manual.
3.3.3 Combustion
Check
IMPORTANT
The heat exchanger metal surfaces may have oil and the
baffle insulation also contains binders. These products will
burn or evaporate when the unit operates for the first time.
Because of that, the smoke reading may be skewed
during the first minutes of operation. Therefore, the unit
must operate during at least 60 minutes before taking any
readings to adjust the combustion quality. Let the unit cool
down before making any adjustments.
IMPORTANT
The combustion check verification MUST be performed
after the nozzle replacement or the burner cleaning. After
these manipulations, the combustion parameters are
necessarily modified. Refer also to the burner instruction
manual.
1.
Pierce a test hole in the flue pipe, approximately 18
inches from the furnace breech. Insert the smoke test
probe into the hole. For installation using a sidewall
venting, use the orifice provided on the breech plate;
2.
From a cold start, let the unit operate for about 5
minutes;
3.
Set the burner air setting until you have between 0
and 1 on the Bacharach Scale (or a “trace”);
4.
Take a CO
2
sample at the same test location where
the #1 smoke reading was taken and make note of it.
Example: 13.8% of CO
2
or 2.5% of O
2
;
5.
Adjust the burner air setting to obtain a CO
2
reading
1.5% lower (or a O
2
reading 2.0% higher) than the
reading associated with the “trace” of smoke.
Example: 12.3% of CO
2
or 4.5% of O
2
;
6.
This method of adjusting the burner will result in clean
combustion (Bacharach smoke scale between 0 and
a trace) and ensure the proper functioning of the
system. The optimum CO
2
level is around 12% to
13% (or 3.5% to 5.0% of O
2
).
3.3.4
Draft Regulator Adjustment
On chimney installations only, a barometric draft regulator
(supplied with the furnace) must be installed, in order to
ensure proper draft through the furnace. The barometric
damper must be mounted with the hinge pins in a
Summary of Contents for AMP112SD
Page 17: ...17 Figure 9 Furnace Dimensions...
Page 18: ...18 Figure 10 Wiring Diagram 4 Speed Motor PSC...
Page 19: ...19 Figure 11 Wiring Diagram Variable Speed Motor ECM...
Page 20: ...20 Figure 12 Parts list with 4 speed motor PSC B50091C...
Page 22: ...22 Figure 13 Parts list with variable speed motor ECM B50092C...
Page 25: ......
Page 42: ...19 Figure 9 Dimensions de la fournaise...
Page 43: ...20 Figure 10 Diagramme lectrique avec moteur 4 vitesses PSC...
Page 44: ...21 Figure 11 Diagramme lectrique avec moteur vitesse variable ECM...
Page 45: ...22 B50091C Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...
Page 47: ...24 B50092C Figure 13 Liste de pi ces avec moteur vitesse variable ECM...