background image

 

 

8

 

 

 

g.  Halogen type refrigerants; 
h.  Cleaning solvents (such as perchloroethylene); 
i. 

Printing inks, paint removers, varnishes, etc. ; 

j. Hydrochloric 

acid; 

k. 

Solvent based glue; 

l. 

Antistatic fabric softeners for clothes dryers; 

m.  Acid based masonry cleaning materials. 

2.8.2  Burner with Outdoor Combustion Air Kit

 

Certain burners are designed to function with combustion air 
taken directly from the outside. Follow the instructions provided 
with the burner, the fresh-air supply kit or the side-wall venting 
kit. 

 

2.9 OIL

 

TANK 

WARNING

 

 

Fire and explosion hazard. 

 

Use only approved heating type oil in this furnace. 
DO NOT USE waste oil, used motor oil, gasoline or 
kerosene. 

 

Use of these will result in death, bodily injury and/or 
property damage. 

 

CAUTION 

 

When a 0.75 USGPH or smaller nozzle is used, a 10 micron or 
finer filter, must be installed on the oil supply line to the 
furnace inside the building where the unit is located. 

 

This is a requirement in order for the heat exchanger warranty 
to remain in force. 

 

Check your local codes for the installation of the oil tank and 
accessories. 

 

At the beginning of each heating season or once a year, check 
the complete oil distribution system for leaks. 

 

Ensure that the tank is full of clean oil. Use No.1 or No.2 
Heating Oil (ASTM D396 U.S.) or in Canada, use No.1 or No.2 
Furnace Oil. 

 

A manual shut-off valve and an oil filter shall be installed in 
sequence from tank to burner. Be sure that the oil line is clean 
before connecting to the burner. The oil line should be 
protected to eliminate any possible damage. Installations 
where the oil tank is below the burner level must employ a two-
pipe fuel supply system with an appropriate fuel pump. A rise 
of 2.4 m (8') and more requires a two stage pump and a rise 
greater than 4.9 m (16') an auxiliary pump.  
 
Follow the pump instructions to determine the size of pipe 
needed in relation to the rise or to the horizontal distance. 

2.10 DUCTING 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

DO NOT draw return air from inside a closet or utility 
room. Return air MUST be sealed to the furnace 
casing. 

 

Failure to properly seal ducts can result in death, 
bodily injury and/or property damage. 

 

The ducting must be designed and installed according to 
approved methods, local and national codes as well as 
good trade practices.  

 

When ducting supplies air to a space other than where the 
furnace is located, the return air must be sealed and also 
be directed to the space other than where the furnace is 
located.  

 

2.10.1 Air 

filter 

 

A properly sized air filter must be installed on the return air 
side of the unit. Refer to the Technical Specifications, 
Table 6 for the correct dimensions. Also refer to Section 
2.2 and the instructions supplied with the filter. 

 

2.11 SUPPLY

 

AIR

 

ADJUSTMENTS

 

 

(4

 

SPEED

 

MOTORS) 

On units equipped with 4-speed blower motors, the supply 
air must be adjusted based on heating/air conditioning 
output and the static pressure of the duct system. For the 
desired air flow refer to the following table as well as the 
air flow tables based on static pressure in the Technical 
Specifications section of this manual. 

Table 1: Blower speed adjustments, 4 speed motor

 

 

FURNACE 

APPLICATION 

HEATING OR A/C  

OUTPUT 

RECOMMENDED 
BLOWER SPEED 

0.68 USGPH 

MED-LOW 

HEATING 

0.80 USGPH 

MED-HIGH 

2.0 TONS 

LOW 

2.5 TONS 

MED-LOW 

3.0 TONS 

MED-HIGH 

A/C 

3.5 TONS 

HIGH 

 

To effect the adjustment, the RED (for heating) and BLUE 
(for cooling and heat pump) wires can be changed on the 
motor. Also, refer to the position of the wires on the 
electronic board of the unit and consult the wiring 
diagrams. If the heating and air conditioning speeds are 
the same, the RED wire must be moved to “UNUSED 
LEADS” on the electronic board and the jumper provided 
with the BLUE wire must be used between the “HEAT” 
and “COOL” terminals. 

 

The blower start/stop delays can be adjusted by 
positioning the DIP switches on the electronic board as 
shown in the following figures. The recommended blower 
ON delay is 60 seconds and blower OFF delay 2 minutes: 

Summary of Contents for AMP112SD

Page 1: ...L FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Attention Do not tamper...

Page 2: ...tilation air openings in a closet door 4 Figure 2 Upflow installation 4 Figure 3 Downflow installation 5 Figure 4 Horizontal installation 5 Figure 5 Thermostat wiring heating and air conditioning with...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to pre...

Page 5: ...TION The exterior of the unit must have an uninterrupted ground to minimize the risk of bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for tha...

Page 6: ...Before starting the burner for the first time adjust the air and turbulator settings to those listed in this manual Once the burner becomes operational final adjustments will be required Refer to sect...

Page 7: ...ormance Test The purpose of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BV...

Page 8: ...distance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal...

Page 9: ...o do so can result in death or bodily injury 2 13 1 Humidifier HUM The 120 VAC HUM terminal on the electronic board of the blower is tied directly to terminal 8 of the 9 terminal connector of the elec...

Page 10: ...n the instructions provided with the burner 3 3 CHECKS AND ADJUSTMENTS 3 3 1 Purging The Oil Line Open the bleed port screw and start the burner Allow the oil to drain into a container for at least 10...

Page 11: ...the obstruction and the burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart After Burner Failure 1 Set the...

Page 12: ...obstruction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish...

Page 13: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 14: ...ard and Canadian regulation 85 5 85 0 85 5 85 0 AFUE From ASHRAE 103 standard and US regulation 85 2 85 0 85 2 85 0 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse...

Page 15: ...nOn D elay CFMLevel Time ShortR unOn Delay C FMLevel Time Off Delay CFMLevel Time A 1 OFF 2 OFF 0 68 13 45sec 19 60sec 38 3min B 1 ON 2 OFF 0 80 13 45sec 19 30sec 38 3min C 1 OFF 2 ON A ll 13 45sec 10...

Page 16: ...ANDWARM AIRDUCTWITHIN6ft OFFURNACE1 5 08 cm 2 2 54cm 1 5 08 cm 2 BOTTOM FURNACE2 2 54cm 1 3 5 08 cm 2 4 BACK FURNACE OP P OSITESIDEOFTHEBURNE R 1 7 62 cm 3 7 62cm 3 7 62 cm 3 PLE NUMORHORIZONTALWARM A...

Page 17: ...17 Figure 9 Furnace Dimensions...

Page 18: ...18 Figure 10 Wiring Diagram 4 Speed Motor PSC...

Page 19: ...19 Figure 11 Wiring Diagram Variable Speed Motor ECM...

Page 20: ...20 Figure 12 Parts list with 4 speed motor PSC B50091C...

Page 21: ...er slide included 32 B03637 02 LATERAL BAFFLE 33 B03480 01 FILTER RACK KIT 34 B03635 FLOOR 35 B03651 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 36 B03653 REAR PANEL ASSEMBLY Pane...

Page 22: ...22 Figure 13 Parts list with variable speed motor ECM B50092C...

Page 23: ...IDE One blower slide included 31 B03637 02 LATERAL BAFFLE 32 B03480 01 FILTER RACK KIT 33 B03635 FLOOR 34 B03651 02 SIDE PANEL ASSEMBLY LEFT Panel insulation and baffle included 35 B03653 REAR PANEL A...

Page 24: ...DER LE DOCUMENT PR S DE L UNIT POUR R F RENCES ULT RIEURES PROPRI TAIRE S V P GARDER CE MANUEL PR S DE L UNIT POUR R F RENCES ULT RIEURES Attention Ne pas alt rer votre unit ou ses contr les Appeler u...

Page 25: ......

Page 26: ...ions et localisation ouvertures de ventilation dans la porte du placard 6 Figure 2 D bit ascendant 6 Figure 3 D bit descendant 6 Figure 4 D bit horizontal 6 Figure 5 Branchement du thermostat chauffag...

Page 27: ...v Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service ayez en main la page de la fiche technique section 5 note de ce manuel...

Page 28: ...s de chauffage air chaud et syst me d air climatis ANSI NFPA 211 Chemin e Foyers vents et appareils de chauffage ANSI NFPA 70 Code National d lectricit CSA C22 1 or CSA C22 10 Code Canadien d lectrici...

Page 29: ...tre install dans le m me sens peu importe l orientation de la fournaise Voir figure 3 pour plus de d tails La plaque de protection B03789 doit tre install e sur le couvercle de plastique du br leur B...

Page 30: ...chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 4 INSTALLATION DU THERMOSTAT L installation d un thermostat de contr le de la temp rature d...

Page 31: ...u br leur pour plus de d tail concernant l ajustement du d lai post purge 2 6 VACUATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone Lire et suivre toutes les instructions contenues d...

Page 32: ...UALIFI 2 8 APPROVISIONNEMENT EN AIR DE COMBUSTION ET VENTILATION MISE EN GARDE Risque d empoisonnement par monoxyde de carbone R f rer aux codes d installation des appareils au mazout ANSI NFPA 31 aux...

Page 33: ...tallations ayant un r servoir de mazout situ sous le niveau du br leur doivent utiliser une ligne de retour de mazout vers le r servoir avec une pompe appropri e une l vation de 2 4 m 8 et plus requi...

Page 34: ...auffage Position interrupteurs DIP 1 2 POSITION Consommation USGPH OFF OFF A 0 68 ON OFF B 0 80 OFF ON C 0 68 ON ON D 0 80 Ajustements suppl mentaires pour une l vation de temp rature de l air sup rie...

Page 35: ...huile est ouverte 5 Le bouton Reset du br leur est bien enfoncer ou r armer 6 L ajustement d air pr liminaire du br leur est conforme aux tableaux des sp cifications de ce manuel 7 L ajustement des v...

Page 36: ...evant du r gulateur la verticale voir les instructions incluses avec le r gulateur Ajuster le r gulateur de tirage apr s que l appareil ait fonctionn e au moins cinq minutes et r gl entre 0 025 et 0 0...

Page 37: ...les fusibles et disjoncteur 3 V rifier si l interrupteur d alimentation principal de la fournaise est en position ON 4 Ajuster le thermostat au dessus de la temp rature ambiante 5 Si l allumage du br...

Page 38: ...tre du r servoir Remplacer le filtre du r servoir au besoin Suivre les instructions du fabriquant Filtre secondaire Remplacer les cartouches des filtres de 10 microns ou moins une fois par ann e Suivr...

Page 39: ...103 et des lois am ricaines 85 2 85 0 85 2 85 0 BR LEUR RIELLO MOD LE 40 BF5 vacuation directe DV Longueur d insertion du tube du br leur pouces Gicleur Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Pr...

Page 40: ...On Niveau PCM Temps D lai Off Niveau PCM Temps A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON Tous 13 45 sec 100 0 sec 100 2 min D 1 ON 2 O...

Page 41: ...ISE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 DESSOUS FOURNAISE 2 2 54 cm 1 3 5 08cm 2 4 ARRI RE FOURNAISE C T OPPOS DUBR LEUR 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PL NUMOU CONDUIT D AIR CHAUDHORIZONTAL 6 pi DE LA F...

Page 42: ...19 Figure 9 Dimensions de la fournaise...

Page 43: ...20 Figure 10 Diagramme lectrique avec moteur 4 vitesses PSC...

Page 44: ...21 Figure 11 Diagramme lectrique avec moteur vitesse variable ECM...

Page 45: ...22 B50091C Figure 12 Liste de pi ces avec moteur 4 vitesses PSC...

Page 46: ...une seule glissi re 32 B03637 02 DEFLECTEUR LATERAL 33 B03480 01 KIT SUPPORT A FILTRE 34 B03635 PLANCHER 35 B03651 02 ASS PANNEAU COTE GAUCHE Comprend panneau isolation et d flecteur 36 B03653 ASS PA...

Page 47: ...24 B50092C Figure 13 Liste de pi ces avec moteur vitesse variable ECM...

Page 48: ...TEUR Comprend une seule glissi re 31 B03637 02 DEFLECTEUR LATERAL 32 B03480 01 KIT SUPPORT A FILTRE 33 B03635 PLANCHER 34 B03651 02 ASS PANNEAU COTE GAUCHE Comprend panneau isolation et d flecteur 35...

Reviews: