87
DENT
Instruments
PowerScout 24
All Things BACnet
Object
Identifier
Name
Description
* System=sum of three phases
3040
Volts L1 to L3
“
3050
Volts L1 to Neutral
Individual Phase to Neutral Voltages (V)
3060
Volts L2 to Neutral
“
3070
Volts L3 to Neutral
“
4010
Amps System Average
Average of all phases.
4020
Amps L1
Individual Phase Currents (A)
4030
Amps L2
“
4040
Amps L3
“
5000
kVAR System
System Total Reactive Power (kVAR). Unsigned absolute (ABS) value
of ABS (kVAR L1) + ABS (kVAR L2) + ABS (kVAR L3)
5001
kVAR System Net
System Total Reactive Power (kVAR). Signed net value of (kVAR L1)
+ (kVAR L2) + (kVAR L3)
5030
kVAR L1
Individual Phase Reactive Energy LSW (kVARh) (Signed)
5060
kVAR L2
“
5090
kVAR L3
“
5120
kVAR Demand System Max
System Maximum Instantaneous kVAR Demand (kVA, resettable). It
displays the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset the value is not reset but
it does not update again until 1 demand window elapses.
(Unsigned/Absolute)
5130
kVAR Demand System Now
Average kVAR demand for most recent window (resettable).
Displays the default value after a CAM or reset, or power cycle.
Updates every min thereafter. True demand value takes a demand
period to get to actual value. (Unsigned/Absolute)
6010
kVARh System
System Total Reactive Energy (Unsigned/Absolute)
7000
kVAh System Total
System Total Apparent Energy (Unsigned/Absolute)
8000
kVA System
System Total Apparent Power (kVA). Unsigned absolute (ABS) value
of ABS (kVA L1) + ABS (kVA L2) + ABS (kVA L3)