84
DENT
Instruments
PowerScout 24
All Things BACnet
Object
Identifier
Name
Description
12080
Service Type
A value of 1 configures the meter for Delta.
A value of 0 configures the meter for Wye.
12090
Line Frequency
Line frequency setting for metering. 50 = 50 Hz, 60 = 60 Hz
12110
Snap Rog Threshold
“Snap to Zero” threshold Rogowski CTs. Register value is:
12120
Snap Volt Threshold
“Snap to Zero” threshold for voltage. Register value is 1x:
12121
CT1 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
12122
CT2 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
12123
CT3 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
12131
CT1 Type
1=MilliVolt, 2=Rogowski
12132
CT2 Type
1=MilliVolt, 2=Rogowski
12133
CT3 Type
1=MilliVolt, 2=Rogowski
12134
CT1 Voltage Source
Individual Phase Voltage Source
12135
CT2 Voltage Source
Individual Phase Voltage Source
12136
CT3 Voltage Source
Individual Phase Voltage Source