63
DENT
Instruments
PowerScout 24
All Things Modbus
45102
5101
I/O port 1 pulse input
accumulator MSW
Scaled pulse MSW
45103
5102
I/O port 1 pulse input scaling
(integer)
Integer scale factor
(Scale = 45103 + 45104/1000)
45104
5103
I/O port 1 pulse input scaling
(decimal)
x1000 decimal fraction of scale factor
45200
5199
Configures the pulse input for
I/O port 2
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling
edges are ignored. If pulse output is enabled, it is
disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising
edges are irnored. If pulse output is enabled, it is
disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse
output is enabled, it is disabled when this
configuration is set. (Note when pulse is off, I/O
control is enabled)
45201
5200
I/O port 2 pulse input
accumulator LSW
Scaled pulse LSW
45202
5201
I/O port 2 pulse input
accumulator MSW
Scaled pulse MSW
45203
5202
I/O port 2 pulse input scaling
(integer)
Integer scale factor
(Scale = 45203 + 45204/1000)
45204
5203
I/O port 2 pulse input scaling
(decimal)
x1000 decimal fraction of scale factor
45302
5301
Port 1 output control when
used as an on/off—open/closed
switch
0 = output LOW (closed)
1 = output HIGH (open) [default]
Register 45310 must = 0 to use
45310
5309
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
45311
5310
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)