72
DENT
Instruments
PowerScout 24
All Things Modbus
N
EGATIVE
P
OWER
/E
NERGY
M
EASUREMENT
R
EGISTERS
Modbus
Offset
Register
Detailed Description
* System=sum of three phases
47001
7000
Negative kWh System LSW
System Negative True Energy LSW (kWh, resettable)
47002
7001
Negative kWh System MSW
System Negative True Energy MSW (kWh, resettable)
47003
7002
Negative kW System
System Negative Instantaneous Negative True Power
(kW) (net sum of all individual kWs, if sum is positive
value=0)
47004
7003
kW Demand System Max
System Maximum Demand (peak demand).
47005
7004
kW Demand System Now
Average Power (kW) for most recent demand window
47006
7005
Negative kW System Max
System Net Highest Instantaneous Negative Draw
Since Reset (kW, resettable)
47007
7006
Negative kW System Min
System Net Lowest Instantaneous Negative Draw
Since Reset (kW, resettable)
47008
7007
Negative kVARh System LSW
System Net Negative Reactive Energy LSW (kVARh,
resettable)
47009
7008
Negative kVARh System MSW
System Net Negative Reactive Energy MSW (kVARh,
resettable)
47010
7009
Negative kVAR System
System Net Instantaneous Negative Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
positive value=0)
47011
7010
kVAh System LSW
System Apparent Energy LSW (kVAh, resettable)
47012
7011
kVAh System MSW
System Apparent Energy MSW (kVAh, resettable)
47013
7012
kVA System
System Instantaneous Apparent Power (kVA)
47014
7013
Negative Displacement PF
System
System Negative Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is Negative, this register will contain that
value else it will be zero)