
85
DENT
Instruments
PowerScout 24
All Things BACnet
P
ULSE
O
UTPUT
/I
NPUT
O
BJECTS
Object
Identifier
Name
Description
13040
Configures the pulse input for
I/O port 1
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
13050
I/O port 1 pulse input
accumulator
Scaled pulse
13060
I/O port 1 pulse input
x1000 decimal fraction of scale factor
13070
Configures the pulse input for
I/O port 2
0 = off, pulse input disabled
1 = rising edge, pulse counter increments, falling edges are ignored. If
pulse output is enabled, it is disabled when this configuration is set.
2 = falling edge, pulse counter increments, rising edges are irnored. If
pulse output is enabled, it is disabled when this configuration is set.
3 = both edges pulse counter increments. If pulse output is enabled,
it is disabled when this configuration is set. (Note when pulse is off,
I/O control is enabled)
13080
I/O port 2 pulse input
accumulator
Scaled pulse
13090
I/O port 2 pulse input scaling
x1000 decimal fraction of scale factor
14014
BBMD IP Address
LSW object identifier
14015
BBMD IP Address
MSW object identifier
15000
Digital Port 1 Configuration
Turns pulses on/off
0 = No pulses, Port may be used as an on/off—
open/closed switch
44001 = System kWh pulses
44008 = System kVARh pulses
44011 = System kVAh pulses
15010
Port 1 pulse output relay type
0 = normally open (HIGH)
1 = normally closed (LOW)