Offset refers to a base of 40001.
Modbus
Offset
Register
Description
* System=sum of three phases
44001
4000
kWh System LSW
System Total True Energy LSW (kWh)
44002
4001
kWh System MSW
System Total True Energy MSW (kWh)
44003
4002
kW System
System Total True Power (kW). Unsigned absolute
(ABS) value of ABS (kW L1) + ABS (kW L2) + ABS (kW
L3)
44004
4003
kW Demand System Max
System Maximum Demand (peak demand).
44005
4004
kW Demand System Now
Average Power (kW) for most recent demand window
44006
4005
kW System Max
System Maximum Instantaneous kW
(Highest kW sample measured)
44007
4006
kW System Min
System Minimum Instantaneous kW
(Lowest kW sample measured)
44008
4007
kVARh System LSW
System Total Reactive Energy LSW (kVARh)
44009
4008
kVARh System MSW
System Total Reactive Energy MSW (kVARh)
44010
4009
kVAR System
System Total Reactive Power (kVAR). Unsigned
absolute (ABS) value of ABS (kVAR L1) + ABS (kVAR L2)
+ ABS (kVAR L3)
44011
4010
kVAh System LSW
System Total Apparent Energy LSW (kVAh)
44012
4011
kVAh System MSW
System Total Apparent Energy MSW (kVAh)
44013
4012
kVA System
System Total Apparent Power (kVA). Unsigned WYE =
(kVA L1) + (kVA L2) + (kVA L3) Delta = SQRT (kW
system ^2 + kVAR system ^2)
44014
4013
Displacement PF System
System Displacement Power Factor (PF). Register is
100x actual value.
44015
4014
Apparent PF System
System Apparent Power Factor (PF). Register is 100x
actual value.
44016
4015
Amps System Avg
Average of all phases.