86
DENT
Instruments
PowerScout 24
All Things BACnet
A
BSOLUTE
/N
ET
V
ALUE
M
EASUREMENT
O
BJECTS
System=sum of three phases.
Object
Identifier
Name
Description
* System=sum of three phases
1000
kW Demand System Maximum
System Maximum Demand (peak demand) (Unsigned/Absolute)
1010
kW Demand System Now
Average Power (kW) for most recent demand window
(Unsigned/Absolute)
1020
kW Demand System Minimum
Min Average power window (kW) (Unsigned/Absolute)
1030
kW System
System True Power (kW). Unsigned absolute (ABS) value of
ABS (kW L1) + ABS (kW L2) + ABS (kW L3)
1031
kW System Net
System Power (kW) Signed net value of (kW L1) + (kW L2) + (kW L3)
1060
kW System Average
Equals kWh System / (Time Since Reset /3600 seconds/Hr)
(resettable)
1100
kW System Maximum
System Highest Instantaneous Draw Since Reset (kW)
1130
kW System Minimum
System Lowest Instantaneous Draw Since Reset (kW, resettable)
1160
kW L1
Individual Phase True Power (kW) (Signed)
1190
kW L2
“
1220
kW L3
“
2000
kWh System Total
System True Energy (kWh) (Unsigned/Absolute)
2021
kWh System Total Net
System True Energy (kWh) (Net)
2051
kWh L1 Net
Individual Phase True Energy (kWh) (Net)
2081
kWh L2 Net
“
2111
kWh L3 Net
“
3000
Volts Line to Line Average
Voltage Line to line Average
3010
Volts Line to Neutral Average
Voltage Line to neutral Average
3020
Volts L1 to L2
Individual Phase to Phase Voltages
3030
Volts L2 to L3
“