61
DENT
Instruments
PowerScout 24
All Things Modbus
Modbus
Offset
Register
Description
44603
4602
Demand Window Size
Demand window size in minutes; default is 15 min
44604
4603
Volts Multiplier Integer
(see 44616 for Volts Multiplier
Decimal)
Multiply volts values by this Volts Multiplier
Decimal/1000. Use with Step-down Transformer.
Affects all parameters that use volts (i.e., kW)
44606
4605
Communication Setting
Baud: 900=9600, 1900=19200, 3800=38400,
5700=57600, 7600 =76800, 11500=115200
Parity: Add 00 = NO, Add 10 = ODD, Add 20 = EVEN
Stop bit: Add 0 = 1 (UART does not permit 0 stop bits),
Add 1 = 1, Add 2 = 2
E.g., 901 = 9600 baud, no parity, 1 stop bit
44607
4606
Service Type
A value of 0x0002 configures the meter for Single
Phase
A value of 0x0001 configures the meter for DELTA
A value of 0x0000 configures the meter for WYE
44609
4608
Set Line Frequency
Line frequency setting for metering: 50=50 Hz,
60=60Hz
44610
4609
Snap Rog Threshold
“Snap to Zero” threshold Rogowski CTs. Register value
is:
44611
4610
Snap Volt Threshold
“Snap to Zero” threshold for voltage. Register value is
1x:
44612
4611
Communications Settings
Write 1833 to change to BACnet mode
44616
4615
Volts Multiplier Decimal
Multiply volts values by (this scalar/1000+Volts
Multiplier Integer). Use with Step-down Transformer.
Affects all parameters that use volts (i.e., kW)
50016
10015
CT1 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
50017
10016
CT2 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
50018
10017
CT3 Rogowski mV/kA
Number of mV per kA for a Rogowski CT
50100
10099
CT1 Integer
Integer part of CT1
50101
10100
CT1 Decimal
Fractional part of NV_CT1
50104
10103
CT1 Voltage Source
Voltage source = Select voltage phase to associate
with CT for power and energy calculations. 0= not
used,1=L1, 2=L2, 3=L3,4=L1-L2,5=L3-L2, 6=L1-L3,
default=L1. Note this register is only active if Service
Type (44607) is set to 2 (Single/Independent)
50105
10104
CT1 Amps Multiplier
Amps multiplier= Multiply amps value by this scalar.
For use with 5A CTs and single leg monitoring of a
three phase load. Affects all parameters that use
amps (e.g., kW). Whole numbers only.
50125
10124
CT1 Type
Select 1=mV or 2=Rogowski CT1s
50199
10198
CT1 Phase Shift
Phase Shift X 100 +/-
50200
10199
CT2 Integer
Integer part of CT2
50201
10200
CT2 Decimal
Fractional part of NV_CT2