PowerScout 24
Field Installation
Using the Pulse Output Port Function
Pulse output is used to generate pulses for external devices such as data loggers that can accept pulses
but do not have BACnet or Modbus capability. The PowerScout 24 can generate pulses based on
accumulated value(s) such as system kWh, system kVARh, and system kVAh. When a pulse is generated
by the meter, the pulse LED will briefly flash, otherwise it will remain dark.
When in Modbus, the pulse output is scaled by the Modbus data scalar register 44602. When in BACnet,
the pulse output is scaled by the CT Pulse Scalar object 12030. The pulse scalar table is the same as the
Modbus data scalar table. For example, when the data scalar is set to 3, each pulse will represent
.1kWh, .1kVAh and .1kVARh.
Data Scalar
Pulse Scalar Value
kWh
kVAh
kVARh
0
.00001
.00001
.00001
1
.001
.001
.001
2
.01
.01
.01
3
.1
.1
.1
4
1
1
1
5
10
10
10
≥6
100
100
100
Table 12: Pulse Scalar Values
For system pulse output:
kWh pulse output—write
44001
into the pulse output configuration object.
kVAh pulse output—write
44011
into the pulse output configuration object.
kVARh pulse output—write
44008
into the pulse output configuration object.