57
DENT
Instruments
PowerScout 24
Field Installation
Resetting BACnet Objects/Modbus
Registers
Many of the PowerScout objects/registers are real-time values such as instantaneous watts or power
factor. However, some objects are accumulated values such as kWh, kVARh, kVAh and various Peak
Demand (kW) values.
To reset all BACnet accumulated objects at once:
Write to object identifier 10140 “Clear Accumulated Values” current value
1234
.
To reset all Modbus accumulated registers at once:
Write to register 44066 “Clear Accumulated Measurements” current value
1234
.
In ViewPoint, accumulating objects/registers can be reset using the
Read/Set
or
Read/Write
tab.
Click
Clear Totals
at the bottom of the screen.
See the tables in the Appendices for a list all of the objects/registers available on the PowerScout
meters.