Chapter 2 Installation and Wiring
|
VFD-L-I Series
Revision July 2009, SW V1.1
2-9
Make sure that the leads are connected correctly and the AC drive is properly grounded.
Use ground leads that comply with local regulations and keep them as short as possible
to prevent electric shock or fire.
Multiple VFD-L-I units can be installed in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below.
Ensure there are
no ground loops.
good
excellent
not allowed
2.4.4 Control Terminals
RA
RC
+10V
AVI
M0
M1
GND
120VAC/DC 28V 3A
Relay Wire gauge: 22-12 AWG
Wire type: Copper only 75℃
Torque: 4 kgf-cm(3.5in-lbf)
Wire gauge: 28-16 AWG
Wire type: Copper only 75℃
Torque: 2 kgf-cm(1.7in-lbf)
Multi-function relay output
Potentiometer power supply
Analog voltage frequency command
Multi-function input terminal
Multi-function input terminal
Digital signal common
Terminal symbols and functions
Terminal
Symbol
Terminal Function
Factory Settings (NPN mode)
ON: Connect to GND
RA
Multi-function Relay output
(N.O.) a
RC
Multi-function Relay common
Output every monitor signal, such as in
operation, frequency attained and overload
indications. Refer to Pr.03-03 for multi-function
output terminals.
+10V
Potentiometer power supply
+10VDC 20mA (variable resistor: 3~5kohm)