Chapter 4 Parameters
|
VFD-L-I Series
Revision July 2009, SW V1.1
4-5
Pr. Explanation
Settings
Factory
Setting
NOTE
04-04
Multi-Function Input Terminal 1 (M0,
M1)
0: No Function
1: M0: FWD/STOP, M1: REV/STOP
2: M0: FWD/REV, M1: RUN/STOP
3: Reserved
4: E.F. External Fault Input (N.O.)
5: E.F. External Fault Input (N.C.)
6: Reset
7: Multi-Step Speed Command 1
8: Multi-Step Speed Command 2
9: Jog Operation
10: Accel/decel Inhibit
11: First or Second
Acceleration/deceleration Time
Selection
1
12: External base block (N.O.)
13: External base block (N.C.)
14: Up: Increment master frequency
15: Down: Decrement master
frequency
16: Run PLC Program
17: Pause PLC Program
18: Counter Trigger Signal
19: Counter Rese
04-05 Reserved
04-06 Reserved
Group 05 Multi-Step Speed and PLC Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
05-00 1st Step Speed Freq.
0.00 to 400.00 Hz
0.00
05-01 2nd Step Speed Freq.
0.00 to 400.00 Hz
0.00
05-02 3rd Step Speed Freq.
0.00 to 400.00 Hz
0.00
05-03 PLC
Mode
0: Disable PLC Operation
1: Stop after executing one program
cycle
2: Continuously execute program
cycles
3: Execute one program cycle step
by step
4: Continuously execute one
program cycle step by step
0
05-04 PLC Forward/ Reverse Motion
0 to 15 (0: FWD 1: REV)
0
05-05 Time Duration of Zero Step Speed
0 to 65500 Sec
0
05-06 Time Duration of 1st Step Speed
0 to 65500 Sec
0
05-07 Time Duration of 2nd Step Speed
0 to 65500 Sec
0
05-08 Time Duration of 3rd Step Speed
0 to 65500 Sec
0
Group 6 Protection Parameters