Chapter 4 Parameters
|
VFD-L-I Series
Revision July 2009, SW V1.1
4-47
Output
F requenc y
Output
Vol tage
0 8- 06
0 8- 05
0 8- 04 =1
0 8- 06
08-05
0 8- 04 =2
Power
Input
Maximum All owable
Power Los s Ti me
B ase bl ock Time
Speed Sear ch
Speed
Sync hr onization
Detec ti on
Maximum
Allowable P ow er
B ase bl ock Time
S pe ed sea rch star ts
wi th th e Ma ster
Fr eq ue ncy
S pe ed sea rch star ts with
Mi n. O utp ut Fr eq ue ncy
08-08
Skip Frequency 1 Upper Limit
Unit: 0.1
08-09
Skip Frequency 1 Lower Limit
Unit: 0.1
08-10
Skip Frequency 2 Upper Limit
Unit: 0.1
08-11
Skip Frequency 2 Lower Limit
Unit: 0.1
08-12
Skip Frequency 3 Upper Limit
Unit: 0.1
08-13
Skip Frequency 3 Lower Limit
Unit: 0.1
Settings
0.0 to 400Hz
Factory Setting: 0.0
These parameters determine Skip frequency. It will cause the AC drive to skip operation at
these frequency ranges with continuous frequency output.
08-14
Auto Restart After Fault
Unit: 1
Settings
0 to 10
Factory Setting: 0
After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can be
reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the
reset/restart operation after any fault has occurred. When enabled, the AC drive will restart
with speed search, which starts at the Master Frequency.
08-15
Automatic Voltage Regulation (AVR)
Factory Setting: 2
Settings
0
AVR function enabled
1
AVR function disabled
2
AVR function disabled when deceleration
The common rating for the motor is 220V/200VAC, 60Hz/50Hz, and the input voltage of the
AC motor drive is 180V~264VAC 50Hz/60Hz. Without AVR function, assume that the input
power of the AC motor drive is 250AC and the output voltage is also 250VAC. It will cause