Chapter 4 Parameters
|
VFD-L-I Series
4-6
Revision July 2009, SW V1.1
Pr. Explanation
Settings
Factory
Setting
NOTE
06-00 Over-Voltage Stall Prevention Level
0: Disable
350 to 410V
390
06-01 Over-Current Stall Prevention Level
0: Disable
20 to 200%
170
0: Disabled
1: Enabled during constant speed
operation. After the over-torque
is detected, keep running.
2: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL2 occurs.
06-02 Over-Torque Detection Mode
3: Enabled during acceleration
operation. After the over-torque
is detected, keep running.
4: Enabled during acceleration
operation. After the over-torque
is detected, keep running until
OL2 occurs.
0
06-03 Over-Torque Detection Level
30 to 200%
150
06-04 Over-Torque Detection Time
0.1 to 10.0 Sec
0.1
06-05
Electronic Thermal Overload Relay
Selection
0: Disable
1: Standard motor
2: Special motor
0
06-06
Electronic Thermal
Characteristic
30 to 600 Sec
60
0: No fault
1: Over current (oc)
06-07
Present Fault Record
2: Over voltage (ov)
3: Over heat (oH)
06-08 Second Most Recent Fault Record
4: Over load (oL)
5: Over load (oL1)
6: External fault (EF)
06-09 Third Most Recent Fault Record
7: Reserved
8: Reserved
06-10 Fourth Most Recent Fault Record
9: Over current during acceleration
(ocA)
06-11 Fifth Most Recent Fault Record
10: Over current during deceleration
(ocd)
06-12 Sixth Most Recent Fault Record
11: Over current during steady state
(ocn)
0
Group 7 Motor Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
07-00 Motor Rated Current
30 to 120%
85
07-01 Motor No-Load Current
0 to 90%
50
07-02 Torque Compensation
0 to 10
1