Chapter 4 Parameters
|
VFD-L-I Series
4-20
Revision July 2009, SW V1.1
2mS
2mS
Preliminary Counter Value Attained Output
(Pr. 03-02=3)
D isplay
(P r.00-04=1)
C ounter Trigger Signal
Multi-function Input Termi nal
Preliminary Counter Value Attained Output
(Pr. 03-02=3)
03-03
Multi-function Output Terminal 1 (Relay)
Unit: 1
Settings 0 to 16
Factory Setting: 8
Setting
Function
Description
0 No
Function
1
AC Drive Operational
the output terminal will be activated when the drive is
running.
2
Setting Frequency Attained
the output will be activated when the AC drive attains the
Setting Frequency.
3
Zero Speed
the output will be activated when Command Frequency
is lower than the Minimum Output Frequency.
4
Over Torque Detection
the output will be activated as long as the over-torque is
detected. Pr.06-03 determines the Over-Torque
detection level and Pr.06-04 determines the Over-
Torque detection time.
5
Base-Block (B.B.) Indication the output will be activated when the output of the AC
drive is shut off by external Baseblock.
6
Low-Voltage Indication
the output will be activated when low voltage is detected.
7
Operation Mode Indication
the output will be activated when the operation of the AC
drive is controlled by External Control Terminals.
8
Fault Indication
the output will be activated when faults occur
9
Desired Frequency Attained the output will be activated when the desired frequency
(Pr.03-00)is attained.
10
PLC Program Running
the output will be activated when the PLC program is
running.
11
PLC Program Step
Completed
the output will be activated for 0.5 sec. when each multi-
step speed is attained.
12
PLC Program Completed
the output will be activated for 0.5 sec. when the PLC
program cycle has completed.