Chapter 4 Parameters
|
VFD-L-I Series
4-8
Revision July 2009, SW V1.1
Group 8 Special Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
08-00 DC Braking Voltage Level
0 to 30%
0
08-01 DC Braking Time during Start-Up
0.0 to 60.0 Sec
0.0
08-02 DC Braking time during Stopping
0.0 to 60.0 Sec
0.0
08-03 Start-Point for DC Braking
0.0 to 400.0 Hz
0.0
0: Operation stops after Momentary
Power Loss
1: Operation continues after
momentary power loss, speed
search starts with the Master
Frequency reference value
08-04
Momentary Power Loss Operation
Selection
2: Operation continues after
momentary power loss, speed
search starts with the minimum
frequency
0
08-05 Maximum Allowable Power Loss Time 0.3 to 5.0 Sec
2.0
08-06 B.B. Time for Speed Search
0.3 to 5.0 Sec
0.5
08-07 Current Limit for Speed Search
30 to 200%
150
08-08 Skip Frequency 1 Upper Limit
0.0 to 400 Hz
0.0
08-09 Skip Frequency 1 Lower Limit
0.0 to 400 Hz
0.0
08-10 Skip Frequency 2 Upper Limit
0.0 to 400 Hz
0.0
08-11 Skip Frequency 2 Lower Limit
0.0 to 400 Hz
0.0
08-12 Skip Frequency 3 Upper Limit
0.0 to 400 Hz
0.0
08-13 Skip Frequency 3 Lower Limit
0.0 to 400 Hz
0.0
08-14 Auto Restart After Fault
0 to 10
0
0: Enable
1: Disable
08-15 AVR
Function
2: Disable when deceleration
2
08-16 Software Braking Level
350 to 450V
380
08-17 DC Braking Lower Bound Limit
0.0 to 400 Sec
0.0
Group 9 Communication Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
09-00
Communication
Address
1 to 247
1
0: Baud Rate 4800 bps
1: Baud Rate 9600 bps
09-01 Transmission Speed
2: Baud Rate 19200 bps
1
0: Warn and Keep Operating
1: Warn and Ramp to Stop
2: Warn and Coast to Stop
09-02
Transmission Fault
Treatment
3: Keep Operating without Warning
0
0: Disable
09-03 Time-out Detection
1 to 20: 1 to 20 sec
0
0: 7,N,2
1: 7,E,1
09-04 Communication
Protocol
ASCII mode
2: 7,O,1
0