Chapter 4 Parameters
|
VFD-L-I Series
4-14
Revision July 2009, SW V1.1
Pr.0 1-09 Pr.0 1-11
Pr.0 1-10
Pr.0 1-12
Fr eq ue ncy
A ccel . Ti me
De cel . Ti me
Time
A ctua l Acce l.( Dece l.) Ti me =
A ccel .(De cel .) Time (O pe ra tio n fr eq ue ncy - Min . ou tp ut fr eq ue ncy)
Ma x. op er ati on fre qu en cy
01-13
Jog Acceleration Time
Unit: 0.01Sec
Settings
0.10 to 600.00Sec
Factory Setting: 10.00
01-14
Jog Deceleration Time
Unit: 0.01Sec
Settings
0.00 to 600.00Sec
Factory Setting: 10.00
01-15
Jog Frequency
Unit: 0.01Hz
Settings
1.00 to 400.00Hz
Factory Setting: 6.00
The JOG function can be selected using Multi-function Input terminals (one of M1~M3) if
programmed for Jog (10). When the Jog terminal is “closed”, the AC drive will accelerate
from Minimum Output Frequency (Pr.01-05) to Jog Frequency (Pr.01-15). When the Jog
terminal “open”, the AC drive will decelerate from Jog Frequency to zero. The
acceleration/deceleration time is decided by the Jog acceleration/deceleration time (Pr.01-13,
01-14). During operation, the AC drive cannot perform Jog command. And during Jog
operation, other operation commands cannot be accepted, except command of FORWARD,
REVERSE and STOP keys on the digital keypad.
O N
O FF
Pr. 01-14
Pr. 01-13
Freque ncy
Time
Max .
Op eration
Freque ncy
J OG
Freque ncy
J OG
Op eration
Comman d
Ac c el. Time
Dec el. Time