Chapter 4 Parameters
|
VFD-L-I Series
4-50
Revision July 2009, SW V1.1
This setting is only valid in ASCII mode. If this function is enabled, time interval between
characters can’t exceed 500ms.
09-04
Communication Protocol
Factory Setting: 0
Settings
0
Modbus
ASCII
mode, protocol <7,N,2>
1
Modbus ASCII mode, protocol <7,E,1>
2
Modbus ASCII mode, protocol <7,O,1>
3
Modbus ASCII mode, protocol <8,N,2>
4
Modbus ASCII mode, protocol <8,E,1>
5
Modbus ASCII mode, protocol <8,O,1>
6
Modbus RTU mode, protocol <8,N,2>
7
Modbus RTU mode, protocol <8,E,1>
8
Modbus RTU mode, protocol <8,O,1>
1. Computer Control
6
1
1: +E V
2: G ND
3: SG -
4: SG +
P in s 1 & 2 a re use d fo r th e p owe r o f di gi tal key pa d.
P le ase do no t use it d ur in g RS -4 85 commu ni ca tio n.
There is a built-in RS-485 serial interface, marked (RJ-11) on the control terminal
block, for VFD-L-I Series. The pins are defined above. Each VFD-L-I AC drive has a
pre-assigned communication address specified by Pr.09-00. The computer then
controls each AC drive according to its communication address.
VFD-L-I can be set to communicate on Modbus networks using one of the following
modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote
Terminal Unit). Users can select the desired mode along with the serial port
communication protocol in Pr.09-04.
Code Description:
ASCII mode:
Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data:
64 Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code
30H
31H
32H
33H
34H
35H
36H
37H
Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’
ASCII code
38H
39H
41H
42H
43H
44H
45H
46H