Dell PowerConnect B-Series TI24X Hardware Installation Guide
15
53-1002265-01
Preparing the installation site
2
Preparing the installation site
Cabling infrastructure
Ensure that the proper cabling is installed in the site. Refer to
for a summary of supported cabling types and their specifications.
Installation location
Before installing the device, plan its location and orientation relative to other devices and
equipment. Allow at least 3 inches of space at the front of the device for the twisted-pair,
fiber-optic, and power cabling to ensure there is no airflow blockage or interference of cable
routing. Also, allow a minimum of 3 inches of space between the sides and the back of the device
and walls or other obstructions.
Installing the device
You can install Dell PowerConnect devices on a desktop or in an equipment rack.
DANGER
Make sure the rack or cabinet housing the device is adequately secured to prevent it from
becoming unstable or falling over.
DANGER
Mount devices in a rack or cabinet as low as possible. Place the heaviest device at the bottom
and progressively lighter devices above.
Desktop installation
Follow the steps for desktop installation.
1. Set the device on a flat desktop, table, or shelf. Make sure that adequate ventilation is
provided for the system. A 3 in. clearance is recommended on each side.
Rack mount installation
For rack mount installation,the Dell PowerConnect B-Series TI24X supports the use of a two post
Telco equipment rack and four post equipment rack.
NOTE
For additional support under the stack of switches. Use Dell 1U shelf, Dell p/n:G118R.