DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
37
12 SPECIFICATION
DC Supply
8.0 V to 35 V Continuous.
Cranking Dropouts
Able to survive 0 V for 50mS, providing supply was at least 10 V before
dropout and supply recovers to 5V
. This is achieved without the need for
internal batteries.
Max. Operating Current
(all inputs & outputs active except
fuel / start)
320mA at 12V, 215mA at 24V
Max. Standby Current
(all inputs & outputs active except
fuel / start)
175mA at 12V, 95mA at 24V
Alternator Input Range
Single phase 2 wire system
3Phase 4Wire System
15 V AC - 300 V AC (ph-N) (+20%)
15 V AC - 300 V AC (ph-N) (+20%)
Alternator Input Frequency
50Hz - 60 Hz at rated engine speed
Magnetic Input Range (if fitted)
+/- 0.5 V to 70 V Peak
Magnetic Input Frequency
10,000 Hz (max) at rated engine speed.
Start Relay Output
16 Amp DC at supply voltage.
Fuel Relay Output
16 Amp DC at supply voltage.
Auxiliary Relay Outputs
5 Amp DC at supply voltage.
Dimensions
240mm x 172mm x 57mm (9.5” x 6.8” x 2.3”)
Panel cut-out
220mm x 160mm ( 8.7” x 6.3”) Maximum panel thickness 8mm (0.3”)
Charge Fail / Excitation Range
0 V to 35 V
Operating Temperature Range
-30 to +70°C
C.T. Burden
2.5VA (see note)
C.T. Secondary
5A
C.T. Class
Class 1 or better recommended
Electromagnetic Compatibility
BS EN 61000-6-2 EMC Generic Emission Standard (Industrial)
BS EN 61000-6-4 EMC Generic Immunity Standard (Industrial)
Electrical Safety
BS EN 60950 Safety of I.T. equipment, including electrical business
equipment.
Cold Temperature
BS EN 60068-2-1 to -30
o
C
Hot Temperature
BS EN 60068-2-2 to +70
o
C
Humidity
BS60068-2-38 to 93% RH @ 40
°
C for 48 Hours
Vibration
BS EN60068-2-6
10 sweeps at 1 octave/minute in each of 3 major axes.
5Hz to 8Hz @ +/-7.5mm constant displacement
8Hz to 500Hz @ 2gn constant acceleration
Shock
BS EN 2011-2-1
3 Half sine shocks in each of 3 major axes
15gn amplitude, 11mS duration
NOTE:- Although the 5110’s burden on the measurement C.T.’s is 2.5VA, the required C.T.
rating will need to be higher depending upon the type and length of cabling used. For further
details see the Appendix section entitled "Choosing the correct C.T.’s” elsewhere in this manual.