DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
25
9.5 LIST
ITEM
SETTINGS
Factory default settings are in
bold italicised
text.
Parameter
Selections
20 - Alternator poles
0,2,
4
,6,8
21 - Oil pressure input
0 - Not used
1 - Digital, close for low
pressure
2 - Digital, open for low
pressure
3 - VDO 0-5bar
4 - VDO 0-10bar
5 - Datcon 5bar
6 - Datcon 10bar
7 - Datcon 7bar
8 - Murphy 7bar
9 - User configured
22 - Coolant temp input
0 - Not used
1 - Digital, close for high
temperature
2 - Digital, open for high
temperature
3 - VDO 40
°
C to 120
°
C
4 - Datcon High
5 - Datcon Low
6 - Murphy
7 - Cummins
8 - PT100
9 - User configured
Parameter
Selections
23 - Fast loading
0 - No
enabled
1 - Yes
24 - AC system
0 - 3 phases 4 wires
1 - 1 phase 2 wire
2 - 3 phases 3 wires
3 - 2 phases 3 wires
25 - Oil pressure
0 - Bar/PSI
display units
1 - kPa
CALL US TODAY
1-888-POWER-58
REQUEST A QUOTE
SHOP ONLINE
www.genpowerusa.com