![Deep Sea Electronics Plc DSE5110 Operating Manual Download Page 14](http://html.mh-extra.com/html/deep-sea-electronics-plc/dse5110/dse5110_operating-manual_2463098014.webp)
14
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
OIL PRESSURE SENDER OPEN CIRCUIT,
if the module detects a loss of signal from the oil pressure
sender (open circuit) a shutdown is initiated. The LCD will indicate:-
(Steady) (And ‘-----‘ on the engine oil pressure instrument). Sender failure is not delayed; it is an
immediate shutdown
.
AUXILIARY INPUTS
, if an auxiliary input has been configured as a shutdown the appropriate LCD
segment will be displayed: -
!
LOSS OF SPEED SIGNAL,
if the speed sensing signal is lost during cranking, a shutdown is initiated.
The
icon will illuminate (Steady). As engine speed cannot be determined, the entire “fail to stop”
timer is observed before the alarm can be reset and the engine restarted.
NOTE:- This will only occur if the controller is configured for magnetic pickup and the speed
sensing signal is lost during cranking or during the safety on timer. If the signal is lost during
normal operation the Generator will shutdown with an Under-speed alarm.