DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
19
6.4 INDICATORS
COMMON ALARM LCD indicators
These indicate when an alarm condition is present. The
Alarm icons or LED’s will detail the exact nature of the
alarm.
(warning) or
(shutdown)
USER CONFIGURABLE LCD INDICATORS
These LCD’s can be configured by the user to indicate
any on of the
different functions
based around the
following:-
•
WARNINGS
and
SHUTDOWNS
- Specific indication
of a particular warning or shutdown condition, backed
up by LCD indication (!)-
Such as Low Oil Pressure
Shutdown, Low Coolant level, etc.
•
STATUS INDICATIONS
- Indication of specific
functions or sequences derived from the modules
operating state -
Such as Safety On, Pre-heating,
Generator Available, etc.
6.5 CONTROLS
STOP/RESET
This button places the module into its
Stop/reset
mode. This will clear any alarm
conditions for which the triggering criteria have been removed. If the engine is running
and this position is selected, the module will automatically instruct the changeover
device to unload the generator
(‘Close generator’ becomes inactive (if used))
. The
fuel supply will be removed and engine will be brought to a standstill. Should a
remote start signal
be present while operating in this mode, a remote start will not
occur.
MANUAL
This mode is used to allow manual control of the generator functions. Once in
Manual
mode
the module will respond to the start (I) button and start the engine and run off
load. If the engine is running off-load in the
Manual mode
and a
remote start signal
becomes present, the module will automatically instruct the changeover device to
place the generator on load
(‘Close generator’ becomes active (if used))
. Should the
remote start signal
then be removed the generator will remain on load until either the
‘STOP/RESET’
or
‘AUTO’
positions is selected.
AUTO
This button places the module into its
‘Automatic’
mode. This mode allows the
module to control the function of the generator automatically. The module will monitor
the
remote start input
and once a start condition is signalled the set will be
automatically started and placed on load
(‘Close generator’ becomes active (if used))
.
If the starting signal is removed the module will automatically transfer the load from the
generator and shut the set down observing the
stop delay timer
and
cooling timer
as
necessary. The module will then await the next start event.
For further details please
see the more detailed description of ‘Auto Operation’ earlier in this manual.
START
This button is only active in MANUAL
mode. Pressing this button in manual mode
will
start the engine and run off load. If the engine is running off-load in the
Manual
mode
and a
remote start signal
becomes present, the module will automatically
instruct the changeover device to place the generator on load
(‘Close generator’
becomes active (if used))
. Should the
remote start signal
then be removed the
generator will remain on load until either the
‘STOP/RESET’
or
‘AUTO’
positions is
selected.
I