DSE Model 5110 Automatic Start Engine Management Instrumentation System
Part No. 057-009 5110 Operating Manual Issue 3.3 3/1/2006
41
16 FACTORY DEFAULT SETTINGS
Modules are shipped from the factory with parameters set to the following values. These can be user
adjusted via the front panel configuration editor. For further details on adjustment via the front panel
editor, see the section entitled “Front panel configuration” elsewhere within this manual.
Parameter
Default
0 - Start delay
5s
1 - Preheat
0s
2 - Crank attempt
10s
3 - Crank rest
10s
4 - Safety delay
8s
5 - Warming up
0s
6 - Return delay
30s
7 - Cooling run
60s
8 - E.T.S. solenoid hold
0s
9 -Sensor fail delay
2s
10 – Fail to Stop Delay
60s
11 - Low Oil Pressure
15PSI
12 - High Temperature
95°C
13 - Under Speed
1250RPM
14 - Over Speed
1750RPM
15 - Underfrequency
40Hz
16 - Overfrequency
57Hz
17 - Charge Alt Failure
8V DC
18 - Flywheel teeth
0 (magnetic pickup disabled)
19 - CT Primary
500A
20 - Alternator poles
4
21 - Oil Pressure transducer
3 - VDO 0-10bar
22 - Coolant temp transducer 2 - VDO 0-120
°
C
23 - Fast loading enabled
0 - No
24 - AC system
3 - 3 phase 4 wire
25 - Oil pressure display units 0 - Bar/PSI
26 - Output 1
1 - Preheat mode 0
27 - Output 2
17 - Common alarm
28 - Output 3
3 - Close generator
29 - LCD 1
9 - Auxiliary input 2 active
30 - LCD 2
10 - Auxiliary input 3 active
31 - LCD 3
11 - Auxiliary input 4 active
32 - LCD 4
12 - Auxiliary input 5 active
33 - Input 1
8 - Remote Start, close to activate
34 - Input 2
0 - Delayed, Warning, close to activate
35 - Input 3
2 - Warning, Immediate, close to activate
36 - Input 4
4 - Delayed, Shutdown, close to activate
37 - Input 5
6 - Immediate, Shutdown, close to activate